Hillsborough, NH’s public water system has regularly exceeded standards for chlorinated disinfection byproducts – both total trihalomethanes and haloacetic acids. In 2011, we were retained to investigate two proposed changes to their chlorine-based treatment system: post-filtration with granular activated carbon; and UV disinfection followed by chloramination.
Bench and pilot-scale testing results favored the UV / chloramine approach. The Town procured the UV equipment directly and awarded a separate installation contract. In June 2014, the UV and chloramine systems were completed and placed on-line. Quarterly sampling taken about 3 weeks later resulted in a 90% TTHM reduction from about 140 to 12 µg/L. Similarly, HAA5 was reduced about 75% from 66 to 17 µg/L. The project was under budget at about $820,000 including equipment, installation and engineering for the 1-mgd system and was financed under the NHDES SRF program.
!["[At Hoyle Tanner] there is a strong encouragement to keep growing professionally, and no one hesitates to help when you have questions or are learning something new. That positive approach to development creates an environment where people feel comfortable challenging themselves and building new skills." - Marko Salih](https://hoyletanner.com/wp-content/uploads/2026/07/Featured-Images_Marko.jpg)